Roof Vents Calculator

Intake & Exhaust Net Free Area Required

How much attic ventilation do I need?

One square foot of net free vent area for every 300 square feet of attic floor, split half intake at the soffits and half exhaust at the ridge. A 1,600 square foot attic needs 5.33 square feet of net free area — 768 square inches — which is 384 square inches each way.

The Roof Vents Calculator computes the Net Free Area (NFA) of intake and exhaust ventilation required by IRC code for your attic. Standard rule: 1 sq ft of NFA per 150 sq ft of attic floor, split 50/50 between intake (soffit vents) and exhaust (ridge vents). Enter attic square footage and the tool returns the NFA needed plus the count of standard ridge and soffit vent pieces. Balanced ventilation prevents ice dams, mold, and premature shingle failure.

Attic ventilation is sized by the 1/300 rule: one square foot of net free vent area for every 300 square feet of attic floor, split evenly between intake at the soffit and exhaust at the ridge. Where there is no vapour barrier, 1/150 applies.

Net free area required by attic size

Ventilation required by attic floor area
Attic floor1/300 total NFAIntake halfExhaust halfRidge vent equivalent
800 sq ft2.7 sq ft (384 sq in)192 sq in192 sq in11 ft of ridge vent
1,200 sq ft4 sq ft (576 sq in)288 sq in288 sq in16 ft of ridge vent
1,600 sq ft5.3 sq ft (768 sq in)384 sq in384 sq in21 ft of ridge vent
2,000 sq ft6.7 sq ft (960 sq in)480 sq in480 sq in27 ft of ridge vent
2,400 sq ft8 sq ft (1,152 sq in)576 sq in576 sq in32 ft of ridge vent

Ridge vent is rated around 18 square inches of net free area per linear foot; soffit vents vary widely, so read the figure printed on the product.

Why the balance matters more than the total

Sizing it by net free area

The attic ventilation calculator works the 1/300 and 1/150 rules through for your attic floor area and converts the result into feet of ridge vent and the number of soffit vents, using the net free area figures printed on the products.

Attic ventilation calculator — net free area needed

Common ventilation mistakes

Checking whether the ventilation is working

The simplest test is temperature. On a hot day a well-ventilated attic sits within roughly 10 to 20 degrees of the outside air; a poorly ventilated one runs far hotter. In winter the tell is frost on the underside of the sheathing, or ice dams along the eaves, both of which mean warm moist air is reaching the deck and condensing.

If the numbers say you have enough vent area but the attic still runs hot, the problem is nearly always intake. Go into the attic with a torch, look along the eaves, and check you can see daylight through the soffit vents. If insulation has been pushed into the eave, baffles at each rafter bay restore the path.

Frequently asked questions

How much attic ventilation do I need?

One square foot of net free vent area per 300 square feet of attic floor when there is a vapour barrier, split half intake and half exhaust. Without a vapour barrier the requirement doubles to 1/150.

How much ridge vent do I need?

Ridge vent gives about 18 square inches of net free area per linear foot. A 1,600 square foot attic needs 5.33 square feet of total net free area, so about 21 feet of ridge vent for the exhaust half.

Can I have too much ridge vent?

Yes. If exhaust exceeds intake the ridge vent starts drawing air in at one end and out the other instead of pulling from the soffits, and in the worst case it pulls conditioned air out of the house.

Why is my attic still hot with a ridge vent?

Almost always blocked intake. Insulation pushed into the eaves closes the soffit vents, and a ridge vent with no intake cannot move air. Baffles at the eave fix it.